Skip to main content Skip to search Skip to main navigation
0
My collective-request products

No products added yet

Go to collective request


Product information

The EWSKD 31.8 3x50/5A 10VA Kl.0,5s is a compact, high-precision low-voltage window-type current transformer of the proven EWSKD series, specially developed for use in power distribution, switchgear, meter panels and industrial measurement and monitoring systems.

Technical main features:
  • Type window-type current transformer (Window-Type) – EWSKD 31.8
  • Transformation ratio 3x 50/5 A (three independent secondary windings, primary rated current 50 A, secondary rated current 5 A)
  • Rated power / burden 10 VA
  • Accuracy class Kl. 0,5 s (according to IEC/EN 61869-2 or DIN EN 61869-2)
  • Primary conductor bore For round conductors up to max. Ø 31 mm (window bore)
  • Maximum operating voltage Um ≤ 0,72 kV
  • Rated frequency 50–60 Hz
  • Thermal rated continuous current Icth = 1,0 × Ipr (continuous current 1 × primary rated current)
  • Thermal rated short-time current Ith = 100 × Ipr, 1 s
  • Insulation class E
  • Insulation test voltage 3 kV, 50 Hz, 1 min
  • Dimensions (approx.) Width 80 mm × height 80 mm × depth 45 mm
  • Weight (approx.) 0,6 kg (depending on version)
  • Mounting Screw mounting, wall or rail mounting possible

The [product name] is characterised by its robust design, high reliability and excellent precision in measurement and protection applications – ideal for applications where accurate monitoring in three-phase systems is required at medium currents (e.g. distribution transformers, control cabinets, energy monitoring systems with higher power requirements).

We are happy to supply this model from stock at short notice or configure further primary currents of the [EWSKD] series for you.

Contact us for your individual quote!


3D models and more files to each product can be found in our download area downloadarea

current transformer knowledge

Background knowledge on the selection, dimensioning and technical parameters of current transformers – prepared in a practical manner.

Read more

current transformer correctly select & dimension

The choice of the suitable current transformer depends on primary current, connection values and purpose of use. This guide leads step by step through the most important selection criteria.

Read more

Accuracy classes for current transformers explained

What do specifications like class 0,5 or 0,2s mean for a current transformer? An overview of the common accuracy classes and their areas of application.

Read more

Stromwandler richtig anschließen

Ein Stromwandler misst nur dann richtig, wenn er in der richtigen Richtung eingebaut und sekundärseitig korrekt verdrahtet ist. Entscheidend sind drei Punkte: Die Primärklemme P1 (K) zeigt zur Einspeisung, die Sekundärkl…

Read more