Art-Nr.: 57585
EASKD 31.5 3x250/5A 10VA Kl.0,5s - Billing current transformer
The Billing current transformer EASKD 31.5 3x250/5A 10VA Kl.0,5s is a compact, high-precision low-voltage measuring transformer of the proven EASKD series, specially developed for use in power distribution, switchgear, meter panels and industrial measurement and monitoring systems.
Technical main features:- Type Billing current transformer (Busbar-Type) – EASKD 31.5
- Transformation ratio 3 × 250/5 A (primary rated current 250 A per phase, secondary rated current 5 A)
- Rated power / burden 10 VA (per phase)
- Accuracy class Kl. 0,5 s (according to IEC/EN 61869-2 or DIN EN 61869-2)
- Primary conductor bore For busbar up to 31.5 mm height
- Maximum operating voltage Um ≤ 0.72 kV
- Rated frequency 50–60 Hz
- Thermal rated continuous current Icth = 1.0 × Ipr (continuous current 1 × primary rated current)
- Thermal rated short-time current Ith = 100 × Ipr, 1 s
- Insulation class E
- Insulation test voltage 3 kV, 50 Hz, 1 min
The EASKD 31.5 3x250/5A 10VA Kl.0,5s is characterized by its compact design for busbar mounting, high accuracy for billing purposes and excellent linearity – ideal for 3-phase applications in distributions with higher currents (e.g. larger switchgear, metering systems, energy monitoring with precise billing).
We will be happy to supply this model from stock at short notice or configure further primary currents of the EASKD series for you.
Contact us for your individual offer!
3D models and more files to each product can be found in our download area downloadarea
current transformer knowledge
Background knowledge on the selection, dimensioning and technical parameters of current transformers – prepared in a practical manner.
Read morecurrent transformer correctly select & dimension
Published on 10 July 2026 · Updated on 31 July 2026
The choice of the suitable current transformer depends on primary current, connection values and purpose of use. This guide leads step by step through the most important selection criteria.
Read moreAccuracy classes for current transformers explained
Published on 10 July 2026 · Updated on 31 July 2026
What do specifications like class 0,5 or 0,2s mean for a current transformer? An overview of the common accuracy classes and their areas of application.
Read moreStromwandler richtig anschließen
Published on 24 September 2026 · Updated on 25 September 2026
Ein Stromwandler misst nur dann richtig, wenn er in der richtigen Richtung eingebaut und sekundärseitig korrekt verdrahtet ist. Entscheidend sind drei Punkte: Die Primärklemme P1 (K) zeigt zur Einspeisung, die Sekundärkl…
Read more