Skip to main content Skip to search Skip to main navigation
0
My collective-request products

No products added yet

Go to collective request


Product information

High-precision all-rounder

The new UMG 96-S2 is suitable for measuring and monitoring electrical parameters and energy consumption as well as for monitoring power quality parameters such as harmonics. Applications can be found in power distribution systems, for example for cost center recording and also limit value monitoring. Furthermore, the device can be used as a measured value transmitter for building management systems or a PLC.


Cost-effective all-rounder
Increase the transparency of your energy data - With the universal measuring device UMG 96-S2

Qualified statements about energy consumption and power quality can only be obtained from measurements that go beyond the feed-in point. To identify sources of interference or energy wasters, data must be recorded at many points in the network. The granularity (resolution) of the measurement is decisive. An ideal solution for this task is the new UMG 96-S2. This energy measuring device stands out as a universally applicable all-rounder.

General

  • Measurement accuracy for voltage, current: 0,2 %
  • Measurement accuracy for active energy (kWh,... / 5 A): class 0,5S

Inputs and outputs

  • Digital output: 1
  • Pulse output

RMS measurement - instantaneous values, e.g.:

  • Current, voltage, frequency
  • Active, reactive, apparent power
  • Power factor

Recording of average values, e.g.:

  • Voltage, current / current and maximum
  • Active, reactive and apparent power / current and maximum
  • Frequency / current and maximum

Power quality measurement

  • Harmonics per order/current and voltage: 1st–15th
  • Distortion factor THD-U / THD-I in %

Interface / protocol

  • RS485 / Modbus RTU

Ambient conditions

  • Temperature range, operation: K55 (-10... +55 °C)

Measuring current input (3 each)

  • Rated current: 1 / 5A
  • Overvoltage category: 300 V CAT II
  • Sampling frequency: 8 kHz

Energy measurement

  • Active, reactive, apparent energy
  • Tariff switching

Measuring voltage input (4 each)

  • Overvoltage category: 300 V CAT III
  • Measuring range, voltage L-N, AC (without transformer): 0 ... 300 Vrms
  • Measuring range, voltage L-L AC (without transformer): 0 ... 425 Vrms
  • Frequency measuring range: 45 ... 65 Hz
  • Sampling frequency per channel (50/60 Hz): 8 kHz
  • Measurement in quadrants: 4
  • Networks: TN, TT

Mechanical properties

  • Net weight (with connectors fitted): approx. 250 g
  • Device dimensions in mm (H x W x D): 96 x 96 x 48
  • Protection rating according to EN 60529 (with seal = IP54): Front IP40 / Rear IP20
  • Mounting according to IEC EN 60999-1/DIN EN 50022: Front panel installation

Network visualization software

  • Free GridVis®-Basic