Skip image gallery
Image similar
Art-Nr.: 5236006
UMG 96-PQ-L Low Power, 90-277V
Product information
Energy measuring device UMG 96-PQ-L-LP
with clock, battery and measurement data memory (64MB)
Panel-mounted device, 96 x 96 x 86 mm (WxHxD)
Supply voltage:90 V - 277 V (50/60) Hz or 90 V - 250 V DC
Installation category: 300 V CAT III
Measurement in TN and TT systems
Measurement of harmonics up to the 65th.
Full-wave events
Active energy accuracy class 0.5S
3 voltage measuring inputs:
Measurement category: 600 V CAT III/300 V CAT IV
Measurement in 3-phase 4-wire systems up to 417 V/720 V (+-10%) according to IEC
Measurement in 1-phase 2-wire systems up to 480 V (+-10%)
4 Low-Power current measuring channels:
Input signal Low-Power circuit: max. 400 mV
Input signal integrator circuit: max. 800mV
Crest factor: 2
Overload for 1 second: 3 V
Resolution: 0.0001 V
Peripherals:
3x digital inputs and outputs each
1x analog output
1x RS485 (Modbus RTU)
Accessories (included):
33.03.890 Installation instructions incl. safety instructions and "Software-GridVis" quick start
52.22.251 Mounting kit
52.00.008 RS485 terminating resistor 120 Ohm
Programming software "GridVis Essentials" download: