Art-Nr.: 5232002
UMG 96-PA, 24-90V
Send question about a product
Company holidays from 1 Sep to 2 Sep – your inquiry will be processed from 3 Sep.
Product information
Energiemessgerät UMG 96-PA with clock, battery and measurement data memory (4MB) Front panel installation device, 96 x 96 x 86 mm (WxHxD) Supply voltage: AC 24 V - 90 V (50/60 Hz) or DC 24 V - 90 V, Installation category: 150 V CAT III Measurement in TN and TT networks Measurement of harmonics up to the 25th 3 voltage measuring inputs: Measurement category: 600 V CAT III Measurement in 3-phase 4-wire systems up to 417 V/720 V (+-10%) according to IEC Measurement in 1-phase 2-wire systems up to 480 V (+-10%) 3 current measuring inputs: Measurement category: 300 V CAT II Rated current 5 A / 1 A adjustable Current measuring range: 5 mA... 6 A Resolution: 0.1 mA Periphery: 3x each digital inputs and outputs 1x analog output 1x RS485 (Modbus RTU) Accessories (included): 33.03.375 Installation instructions incl. safety instructions and "GridVis software" quick start 52.22.251 Mounting kit 52.00.008 RS485 terminating resistor 120 Ohm Programming software "GridVis Basic" download: www.janitza.de/gridvis-download.html