Skip to main content Skip to search Skip to main navigation
0
My collective-request products

No products added yet

Go to collective request


Product information

All-IN-ONE energy monitoring solution - Highly available data-secure communication

Transparency across all data levels is a key success factor for modern companies. Recording and consolidating data from all areas of the company is necessary to optimize planning for e.g. production processes, establish safety measures to protect systems and machines, and save costs.

This goal involves many challenges, as different standards, interfaces and communication options must be coordinated. Networking previously isolated areas, from the machine level, through ERP systems to building management systems, is very time-consuming. OPC UA is a standardization of data transmission that simplifies this consolidation.

The Janitza energy measuring device UMG 801 offers various communication interfaces and enables direct data transmission via OPC UA to higher-level systems, eliminating costly integration.

The modularly expandable UMG 801 is ideally suited for the complete recording of an energy management system (according to ISO 50001). You gain transparency over the energy consumption and energy costs of all measuring levels. In addition, critical deviations in power quality as well as residual currents (RCM) that put a strain on or even endanger systems can be detected.

Future-proof investment: subsequent expansion of measuring points to up to 92 measuring channels is ensured by easily integrable current measuring modules.


Modularly expandable energy measuring device UMG 801 for setting up an energy monitoring system with OPC UA interface DIN rail mounted device

  • 145 x 90 x 76 mm (WxHxD) Supply voltage: External supply voltage 24 V DC Measurement in TN, IT and TT systems Measurement of harmonics up to the 127th. Measurement data memory (4 GB)
  • 3 voltage measuring inputs Measuring category: 1000 V CAT III
  • Measurement in 3-phase 4-wire systems up to 480 V/830 V (+-10%) according to IEC
  • Measurement in 3-phase 3-wire systems up to 690 V (+-10%) 8 current measuring inputs, divided into 2 groups of four
  • Measuring category: 300V CAT II
  • Rated current 5A / 1A adjustable
  • Current measuring range: 5 mA... 6 A
  • Resolution: 0.1mA 4
  • Multifunction inputs Optionally configurable as residual current inputs, temperature inputs or current measuring inputs
  • Peripherals 4x digital inputs 4x digital outputs 1x analog output 2x Ethernet RJ45
  • Accessories (included): 33.03.376 Installation instructions incl. safety information 52.31.205 Bus connector base device (already plugged in) 10.01.953 End bracket
  • Programming software “GridVis Essential” download: www.janitza.de/gridvis-download.html
Properties
Type-Name: UMG
Type number: 801
ambient temperature: -10 - +55 °C
interface: Ethernet, Modbus Gateway, Modbus RTU, Modbus TCP/IP, RS485, USB 2.0
power supply: 24 - 48 VDC external
protection rating: Housing IP 20