Art-Nr.: 14.01.626
Überwachungsmodul 20 CM-CT6 für Betriebs- und Differenzstrome
The operating and residual current monitoring module 20CM-CT6 is intended for use in the industrial sector, in data centers and commercially used buildings. It serves the measurement and calculation of electrical quantities, such as operating and residual current, power, energy and harmonics. Typical areas of application are found in building installation on distributors, circuit breakers and busbar distributors.
Module 20CM-CT6 at a glance
- The module 20CM-CT6 serves to expand the basic device UMG 20CM
- A maximum of 16 modules with 6 channels each (up to 96 channels in total) can be added
- The measurement data of all modules is displayed via the UMG 20CM
- Internal communication and supply via CAN-Bus interface
- Measured value acquisition via integrated current transformers
- Memory for historical data
- RCM diagnostic variables on board
- Display of the status of the limit value monitoring with the help of 6 LEDs
Accessories
- LCAN-RS45 incl. cable and plug
(optional): Article no. 08.02.447 - Separate power supply unit with 24 V DC required
| Properties |
|---|
| Dimension (BxHxT mm): | 119 x 47 x 45 |
|---|---|
| Display: | LED |
| accuracy class: | 0,5% |
| ambient temperature: | -10 - +55 °C |
| flammability class: | UL - V0 |
| frequency range: | 45 - 65 Hz |
| interface: | CAN, CAN 2.0 |
| measuring channels: | x6 |
| measuring range: | 2 mA - 63 A |
| mounting: | Mounting rail 35 mm, for DIN rail to IEC/EN 60715 |
| pickup/release delay: | 0 - 650 s |
| power supply: | 24 VDC (± 10 %, PELV) |
| protection rating: | Housing IP 20 |
| storage temperature: | -25 - +70 °C |
| transformation ratio: | 700:1 |