Art-Nr.: 11-1209
XKBU 812 750/1A 2,5VA Kl.0,5
The XKBU 812 750/1A 2,5VA Kl.0,5 is a compact, high-precision high-frequency split-core current transformer of the proven XKBU series, specifically developed for use in power distribution, switchgear, meter panels and industrial measurement and monitoring systems.
Key technical features:- Type high-frequency split-core current transformer – XKBU 812
- Transformation ratio 750/1 A (primary rated current 750 A, secondary rated current 1 A)
- Rated power / burden 2,5 VA
- Accuracy class Kl. 0,5 (according to IEC/EN 61869-2 or DIN EN 61869-2)
- Maximum operating voltage Um ≤ 0,72 kV
- Rated frequency 50–60 Hz
- Thermal rated continuous current Icth = 1,0 × Ipr (continuous current 1 × primary rated current)
- Thermal rated short-time current Ith = 60 × Ipr, 1 s
- Insulation class E
- Insulation test voltage 3 kV, 50 Hz, 1 min
The XKBU 812 750/1A 2,5VA Kl.0,5 is characterised by its very compact design, high reliability and excellent linearity – ideal for applications where precise measurement is required at higher primary currents (e.g. split-core scenarios, measuring stations, energy monitoring systems with moderate power requirements).
We are happy to supply this model from stock at short notice or configure further primary currents of the XKBU series for you.
Contact us for your individual quotation!
3D models and more files to each product can be found in our download area downloadarea
| Properties |
|---|
| Type-Name: | XKBU |
|---|---|
| Type number: | 812 |
| accuracy class: | 0,5 |
| apparent power (VA): | 2,5 |
| primary current: | 750 |
| secondary current: | 1 |