The universal current transformer (AC/DC) AC/DC CCT 63.5 I is a compact, high-precision low-voltage measuring transformer of the proven CCT series, specially developed for use in power distribution, switchgear, meter panels and industrial measurement and monitoring systems.

Technical main features:
  • Type universal current transformer (AC/DC) – CCT 63.5 I
  • Primary conductor bore For round conductors up to max. Ø 30 mm (window bore)
  • Maximum operating voltage Um ≤ 0.72 kV
  • Rated frequency DC to 5 kHz (AC 50–60 Hz)
  • Thermal rated continuous current Icth = 1.0 × Ipr (continuous current 1 × primary rated current)
  • Thermal rated short-time current Ith = 60 × Ipr, 1 s
  • Insulation class E
  • Insulation test voltage 3 kV, 50 Hz, 1 min
  • Dimensions (approx.) Width 80 mm × height 60 mm × depth 40 mm
  • Weight (approx.) 0.4–0.6 kg (depending on version)
  • Mounting Split-core clamp mounting for easy retrofitting, incl. insulating protective cap

The universal current transformer (AC/DC) AC/DC CCT 63.5 I is characterised by its very compact design, high reliability and excellent linearity – ideal for applications where precise measurement is required for AC and DC currents (e.g. renewable energies, EV charging stations, measuring points with variable currents).

We are happy to supply this model from stock at short notice or configure further variants of the CCT series for you.

Contact us for your individual quote!


3D models and more files to each product can be found in our download area downloadarea

current transformer knowledge

Background knowledge on the selection, dimensioning and technical parameters of current transformers – prepared in a practical manner.

Read more

current transformer correctly select & dimension

The choice of the suitable current transformer depends on primary current, connection values and purpose of use. This guide leads step by step through the most important selection criteria.

Read more

Accuracy classes for current transformers explained

What do specifications like class 0,5 or 0,2s mean for a current transformer? An overview of the common accuracy classes and their areas of application.

Read more

Stromwandler richtig anschließen

Ein Stromwandler misst nur dann richtig, wenn er in der richtigen Richtung eingebaut und sekundärseitig korrekt verdrahtet ist. Entscheidend sind drei Punkte: Die Primärklemme P1 (K) zeigt zur Einspeisung, die Sekundärkl…

Read more

Current transformer for photovoltaic systems

In current measurement in PV systems, current transformers are used for recording feed-in, reference and consumption currents. Here you will learn what to pay attention to when selecting and dimensioning.

Read more