Art-Nr.: 57624
EASKD 31.5 2U 3x600-300/5A 10-5VA Kl.0,5s - Verrechnungsstromwandler
The billing current transformer EASKD 31.5 2U 3x600-300/5A 10-5VA Kl.0,5s is a compact, high-precision low-voltage instrument transformer from the proven EASKD series that can be switched between two primary currents, specially developed for use in power distribution, switchgear, meter panels and industrial measurement and monitoring systems.
Key technical features:- Type billing current transformer (window-type) – EASKD 31.5 2U
- Transformation ratio 3 × (600-300)/5 A (variable rated primary current 300–600 A per unit, rated secondary current 5 A)
- Rated power / burden 10/5 VA
- Accuracy class Kl. 0,5 s (according to IEC/EN 61869-2 or DIN EN 61869-2)
- Primary conductor bore For busbars or round conductors up to max. 31.5 mm height (2U version)
- Maximum operating voltage Um ≤ 0.72 kV
- Rated frequency 50–60 Hz
- Thermal rated continuous current Icth = 1.0 × Ipr (continuous current 1 × rated primary current)
- Thermal rated short-time current Ith = 60 × Ipr, 1 s
- Insulation class E
- Insulation test voltage 3 kV, 50 Hz, 1 min
- Mounting Rail and screw mounting possible, including insulating protective cap
The EASKD 31.5 2U 3x600-300/5A 10-5VA Kl.0,5s is characterised by its very compact design, high reliability and excellent linearity – ideal for applications where precise billing measurement is required at variable medium currents (e.g. larger distribution boards, measuring stations, energy monitoring systems with moderate to higher power requirements).
We are happy to supply this model from stock at short notice or configure further primary currents of the EASKD series for you.
Contact us for your individual quote!
3D models and more files to each product can be found in our download area downloadarea
| Properties |
|---|
| Type-Name: | EASKD |
|---|---|
| Type number: | 31.5 2U |
| accuracy class: | 0,5s |
| apparent power (VA): | 10-5 |
| primary current: | 3x600-300 |
| secondary current: | 5 |