With the making of the connections to the three phases and the neutral conductor, the relay picks up in the fault-free case and the LEDs light up. The prerequisite for this, however, is that the RMS value of the monitored voltage moves within the set window voltage, i.e. this is not greater than Uso and not smaller than Usu. The device also includes a phase sequence display [LED green = right rotating field, LED yellow = left rotating field]. In the fault-free state, all LEDs light up green. Fault messages are indicated by means of a red flashing LED. [L1-L2-L3-N]
Properties
Dimension (BxHxT mm): 17,8 x 90,0 x 76,5, incl. snap foot
Display: LED
Output: 2 changeover contacts, potential-free
Permissible Tolerance: 70%...110% UN
Setting range of the setpoint: U < 150 - 220 VAC, U > 242 - 275,5VAC
Type-Name: UR
Type number: 3067
ambient temperature: -25 - +60 °C
connection voltage: 230/400 VAC 3~/N
dielectric strength: 1 kV AC 50/60 Hz, open contact, 4 kV AC 50/60 Hz, between coil and contact
frequency: 50 Hz
mounting: Mounting rail 35 mm, for DIN rail to IEC/EN 60715
power consumption: < 1 VA
protection rating: Enclosure IP 40
rated operating power: approx. 3 VA
response time: 0,5 s
switching current (max.): 5 A
switching hysteresis: approx. 5 %
switching voltage (max.): 250 VAC / 30 VDC