UR 3066 Unterspannungsmessrelais
Product information
With the application of the 3 phases L1-L2-L3 and the N conductor, the built-in relay (2 changeover contacts) must pick up and the green LEDs light up. If the rated voltage fails or falls below, or if one or more of the 3 phases or the N conductor fails, the corresponding LED flashes and the relay returns to its rest position.
Monitoring in a single-phase network is carried out with the connections L and N.
The type UR 3066 corresponds in its function to the type UR 3060, but is additionally equipped with a phase sequence display [LED green = right phase sequence, LED yellow = left phase sequence]. Additionally, there is a rotary switch for the undervoltage setting range and a rotary switch for setting the pickup delay time. The failure of one or more phases or the N conductor is indicated by a red, flashing LED. In fault-free operation, these LEDs are green.
| Properties |
|---|
| Dimension (BxHxT mm): | 17,8 x 90,0 x 76,5, incl. snap foot |
|---|---|
| Display: | LED |
| Output: | 2 changeover contacts, potential-free |
| Permissible Tolerance: | 70%...110% UN |
| Setting range of the pickup delay: | 0,5 - 15 s |
| Setting range of the setpoint: | 0,65 - 0,95 UN |
| Type-Name: | UR |
| Type number: | 3066 |
| ambient temperature: | -25 - +60 °C |
| connection voltage: | 230/400 VAC 3~/N |
| mounting: | Mounting rail 35 mm, for DIN rail according to IEC/EN 60175 |
| power consumption: | < 1 VA |
| protection rating: | Enclosure IP 40 |
| switching current (max.): | 5 A |
| switching voltage (max.): | 250 VAC / 30 VDC |