Product information
With the application of the 3 phases L1-L2-L3 and the N conductor, the built-in relay (2 changeover contacts) must pick up and the green LEDs light up. If the rated voltage fails or falls below, or if one or more of the 3 phases or the N conductor fails, the corresponding LED flashes and the relay returns to its rest position. Monitoring in a single-phase network is carried out with the connections L and N. The type UR 3066 corresponds in its function to the type UR 3060, but is additionally equipped with a phase sequence display [LED green = right phase sequence, LED yellow = left phase sequence]. Additionally, there is a rotary switch for the undervoltage setting range and a rotary switch for setting the pickup delay time. The failure of one or more phases or the N conductor is indicated by a red, flashing LED. In fault-free operation, these LEDs are green.
Properties
Dimension (BxHxT mm): 17,8 x 90,0 x 76,5, incl. snap foot
Display: LED
Output: 2 changeover contacts, potential-free
Permissible Tolerance: 70%...110% UN
Setting range of the pickup delay: 0,5 - 15 s
Setting range of the setpoint: 0,65 - 0,95 UN
Type-Name: UR
Type number: 3066
ambient temperature: -25 - +60 °C
connection voltage: 230/400 VAC 3~/N
mounting: Mounting rail 35 mm, for DIN rail according to IEC/EN 60175
power consumption: < 1 VA
protection rating: Enclosure IP 40
switching current (max.): 5 A
switching voltage (max.): 250 VAC / 30 VDC