UR 3060 Unterspannungsmessrelais
Product information
With the application of the 3 phases L1-L2-L3 and the N conductor, the built-in relay (2 changeover contacts) must pick up and the green LEDs must light up. However, the prerequisite for this is that the voltage does not fall below the setpoint UN 0,85 (type UR 3060).
If the rated voltage fails or falls below, or if one or more of the 3 phases or the N conductor fails, the corresponding LED flashes and the relay returns to its rest position.
Monitoring in a 1-phase network is carried out with the connections L and N. The failure of one or more phases or the N conductor is indicated by a red, flashing LED. In fault-free operation, these LEDs are green.
| Properties |
|---|
| Dimension (BxHxT mm): | 17,8 x 90,0 x 76,5, incl. snap foot |
|---|---|
| Display: | LED |
| Output: | 2 changeover contacts, potential-free |
| Permissible Tolerance: | 70%...110% UN |
| Setting range of the pickup delay: | 0,5 s fixed |
| Setting range of the setpoint: | 0,85 UN fixed |
| Type-Name: | UR |
| Type number: | 3060 |
| ambient temperature: | -25 - +60 °C |
| connection voltage: | 230/400 VAC 3~/N |
| mounting: | Mounting rail 35 mm, for DIN rail according to IEC/EN 60175 |
| power consumption: | < 1 VA |
| protection rating: | Enclosure IP 40 |
| switching current (max.): | 5 A |
| switching voltage (max.): | 250 VAC / 30 VDC |