Skip image gallery
Image similar
Art-Nr.: 6000140
Stromschienen-Abgang. AKM 96RMPN-530
Product information
Busbar outgoing box AKM 96RMPN-530 for busbar distributor system Siemens BD-2Measuring device: UMG 96RM-PN with viewing window for displayEthernet interface: 2 x RJ45RS485 interface: 2 x M12Measuring device protection: circuit breaker PKZM0-10Fuse load side: NH fuse-disconnector max. protection 530A (fuses not included in scope of delivery)Current measurement: 4 x transformer 600A / 5A Kl.1, 3 phases + NResidual current measurement: transformer CT-AC RCM 140N for measurement of residual currents type ATemperature measurement: 1 x PT100Dimensions outgoing box: approx. 862 x 406 x 352 mm³Note: Options must always be ordered together with the basic device, subsequent retrofitting is not possible.