Skip image gallery
Image similar
Art-Nr.: 6000102
Stromschienen-Abgang. AKM 96RME-250
Product information
Busbar outgoing box AKM 96RME-250 for busbar distributor system Siemens BD-2Measuring device: UMG 96RM-E with viewing window for displayEthernet interface: 1x RJ45RS485 interface: 2x M12Measuring device protection: circuit breaker fuse load side: NH fuse-disconnect switch, max. protection 250 A (fuses not included in scope of delivery)Current measurement: 4x transformer 250A/5A accuracy class 1, 3 phases + NResidual current measurement: transformer CT-AC RCM 80N for measurement of residual currents type ATemperature measurement: 1x PT100Dimensions outgoing box: ( W x H x D ) approx. 662 x 406 x 202 mm³Note: Options must always be ordered together with the basic device, subsequent retrofitting is not possible.