Skip image gallery
Image similar
Art-Nr.: 6000101
Stromschienen-Abgang. AKM 96RME-125
Product information
Stromschienen-Abgangskasten AKM 96RME-125 für Schienenverteiler System Siemens BD-2Measuring device: UMG 96RM-E with viewing window for displayEthernet interface: 1x RJ45RS485 interface: 2x M12Measuring device protection: circuit breaker fuse load side: NH fuse holder 3-phase, max. protection 125 A (fuses not included in scope of delivery)Current measurement: 4x transformer 150A/5A Kl.1, 3 phases + NResidual current measurement: transformer CT-AC RCM 35N for measurement of residual currents type ATemperature measurement: 1x PT100Dimensions outgoing box: ( B x H x T) approx. 530 x 310 x 100 mm³Note: Options must always be ordered together with the basic device, subsequent retrofitting is not possible.