Product information
Busbar outgoing box AKM 96PQL-250 for busbar trunking system Siemens BD-2Measuring device: UMG 96-PQ-L with plug-on module 96-PA-RCM-ELoperable from outside via viewing window with the box closedEthernet interface: 1x RJ45RS485 interface: 2 x M12Measuring device protection: circuit breaker MS 6.3Load side fuse: NH fuse-disconnectormax. protection 250 A (fuses not included in scope of delivery)Current measurement: 4 x current transformer 250A / 5A accuracy class 1, 3 phases + NResidual current measurement: current transformer CT-AC RCM 80Nfor the measurement of residual currents type ATemperature measurement: 1 x PT100Dimensions outgoing box: approx. 662 x 406 x 202mm³Note: Options must always be ordered together with the basic device, subsequent retrofitting is not possible.