Skip to main content Skip to search Skip to main navigation
0
My collective-request products

No products added yet

Go to collective request


Product information
Busbar outgoing box AKM 96PAMIDPLUS-125 for busbar distributor system Siemens BD-2Measuring device: UMG 96-PA-MID+ with module 96-PA-RCM-ELViewing window for display operation from outsideEthernet interface: 1 x RJ45RS485 interface: 2 x M12Measuring device protection: circuit breaker PKZM0-10Fuse load side: NH fuse holder 3-phase,max. protection 125 A (fuses not included in scope of delivery)Current measurement: 4x current transformer for billing purposes 200A / 5A accuracy class 0.5, 3 phases + NResidual current measurement: current transformer CT-AC RCM 35N for measurement of residual currents type ATemperature measurement: 1 x PT100Dimensions outgoing box: approx. 530 x 310 x 100 mm³Note: Options must always be ordered together with the basic device, subsequent retrofitting is not possible.