Measurement functions measuring range Display range Resolution Accuracy
Voltage 0 V…500 V 0 V…500 V from 0.1 V from ±(2% of rdg. + 2 digits)
Frequency 45.0 Hz…65.0 Hz 45.0 Hz…65.0 Hz 0.1 Hz ±(0.1% of rdg. + 1 digit)
Short-circuit loop impedance
2-wire method - measurement with standard current max. current 13.3 A from 0.13 Ω…1999 Ω according to EN 61557 0.00 Ω…1999 Ω from 0.01 Ω ±(5% of rdg. + 3 digits)
2-wire method - measurement without RCD tripping from 0.5 Ω…1999 Ω according to EN 61557 0.00 Ω…1999 Ω from 0.01 Ω from ±(6% of rdg. + 5 digits)
Short-circuit current display
2-wire method - measurement with standard current Can be calculated from the ZS measuring ranges and the rated voltages 0.110 A…9999 A from 0.001 A Calculated from the short-circuit error
2-wire method - measurement without RCD tripping Can be calculated from the ZS measuring ranges and the rated voltages 0.110 A…9999 A from 0.001 A Calculated from the short-circuit error
Low voltage measurement - continuity measurement
Continuity measurement of grounding and equipotential bonding conductors with current ±200 mA 0.12 Ω…400 Ω according to EN 61557-4 0.00 Ω…400 Ω from 0.01 Ω ±(2% of rdg. + 3 digits)
Resistance measurement with low current 0.0 Ω…1999 Ω 0.0 Ω…1999 Ω from 0.1 Ω ±(3% of
Product information

The MZC-304F model is one of the smallest available devices for measuring loop impedance in 230/400 V networks – ideal for installers who also want to test the continuity of protective and equipotential bonding connections. It enables highly accurate loop measurements with a resolution of 0,01 Ω – even in protected circuits with RCD ≥30 mA.

Thanks to the backlit display and illuminated keypad, the device is ideally suited for use in poor lighting conditions. A robust, waterproof housing with protection rating IP67 reliably protects the device even under harsh outdoor operating conditions.

Of course, the MZC-304F meets the requirements of standard EN 61557.


Technical highlights

  • High resolution for loop impedance measurements: 0,01 Ω

  • Safe operation even in RCD-protected circuits ≥30 mA (180–270 V)

  • Voltage ranges: 180–460 V for ZL-L, 180–270 V for ZL-PE and ZL-N

  • Supported network systems: 220/380 V, 230/400 V, 240/415 V

  • Frequency range: 45–65 Hz

  • Short-circuit current calculation (Ik)

  • Also suitable for use with swapped L and N conductors

  • Measurement of resistance (RS) and reactance (XS)

  • Continuity test at low voltage


Additional functions

  • PE conductor test via integrated touch electrode

  • Voltage measurement up to 500 V AC

  • Frequency measurement: 45,0–65,0 Hz

  • Data memory for up to 990 measured values

  • Wireless communication via Bluetooth

  • Operation with 4x LR14 batteries or 4x NiMH rechargeable batteries


Applications

The MZC-304F is ideally suited for testing in buildings with low-voltage installations – from residential buildings and office complexes to small industrial operations. Maintenance teams also benefit from the device’s reliable performance, for example in systems with potential short-circuit currents up to 4,4 kA. The device is also particularly suitable for networks protected by RCD/RCB devices – an indispensable tool for modern electrical testing in accordance with EN 61557.

Properties
Humidity max.: 90%
electromagnetic compatibility (EMV): EN 61326-2-2, IEC/EN 61326-1
interface: Bluetooth
measurement category: CAT III 600 V, CAT IV 300 V
operating temperature: 0 °C - +50 °C
power supply: 4x batteries 1,5 V, 4x batteries 1,5 V, NiMH or LR6
protection rating: Enclosure IP 67
storage temperature: -20 - +70 °C
Weight: 0.8 kg
Width: 102 mm
Height: 220 mm
Measurement functions measuring range Display range Resolution Accuracy
Voltage 0 V…500 V 0 V…500 V from 0.1 V from ±(2% of rdg. + 2 digits)
Frequency 45.0 Hz…65.0 Hz 45.0 Hz…65.0 Hz 0.1 Hz ±(0.1% of rdg. + 1 digit)
Short-circuit loop impedance
2-wire method - measurement with standard current max. current 13.3 A from 0.13 Ω…1999 Ω according to EN 61557 0.00 Ω…1999 Ω from 0.01 Ω ±(5% of rdg. + 3 digits)
2-wire method - measurement without RCD tripping from 0.5 Ω…1999 Ω according to EN 61557 0.00 Ω…1999 Ω from 0.01 Ω from ±(6% of rdg. + 5 digits)
Short-circuit current display
2-wire method - measurement with standard current Can be calculated from the ZS measuring ranges and the rated voltages 0.110 A…9999 A from 0.001 A Calculated from the short-circuit error
2-wire method - measurement without RCD tripping Can be calculated from the ZS measuring ranges and the rated voltages 0.110 A…9999 A from 0.001 A Calculated from the short-circuit error
Low voltage measurement - continuity measurement
Continuity measurement of grounding and equipotential bonding conductors with current ±200 mA 0.12 Ω…400 Ω according to EN 61557-4 0.00 Ω…400 Ω from 0.01 Ω ±(2% of rdg. + 3 digits)
Resistance measurement with low current 0.0 Ω…1999 Ω 0.0 Ω…1999 Ω from 0.1 Ω ±(3% of