Skip to main content Skip to search Skip to main navigation
0
My collective-request products

No products added yet

Go to collective request


Measurement functions Measuring range Display range Resolution Accuracy
Fault loop impedance
Fault loop ZL-PE, ZL-N, ZL-L 0.13 Ω…1999.9 Ω according to IEC 61557 0.00 Ω…1999 Ω from 0.001 Ω ±(5% v.Mw. + 30 Digits)
Fault loop ZL-PE in RCD mode from 0.50 Ω…1999 Ω according to IEC 61557 0.00 Ω…1999 Ω from 0.01 Ω from ±(6% v.Mw. + 5 Digits)
Measuring RCD parameters
RCD trip test and measuring trip time tA test current 0 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
RCD general and short-time delayed 0 ms…300 ms 0 ms…300 ms 1 ms from ±(2% v.Mw. + 2 Digits)
RCD selective 0 ms…500 ms 0 ms…500 ms 1 ms from ±(2% v.Mw. + 2 Digits)
Measuring RCD trip current RCD IA test current 0.2 IΔn…2.0 IΔn
with sinusoidal residual current (type AC) 3.3 mA…1000 mA 3.3 mA…1000 mA from 0.1 mA ±5% IΔn
with pulsating DC currents and with 6 mA DC bias (type A) 3.5 mA…700 mA 3.5 mA…700 mA from 0.1 mA ±10% IΔn
with residual DC current (type B) 2.0 mA…1000 mA 2.0 mA…
Product information

The Sonel MPI-540 is a modern multifunction tester for the comprehensive analysis of electrical installations in residential and industrial areas. It enables all relevant safety and function measurements – with just one device. In addition, electrical grid parameters can be recorded and evaluated, including power quality and protective measures against electric shock.

Thanks to the auto mode for RCD tests as well as preconfigured and individually extendable autotests, test processes can be automated efficiently. With the optional adapter AUTO ISO-1000C, automatic insulation testing on 3-, 4- and 5-core cables becomes child’s play.


More than a tester – your all-in-one solution

  • Huge 7" touch display – best overview and intuitive operation

  • Removable SD card – easy memory expansion

  • Powerful Li-ion battery – long operating time, more efficient work

  • Data logger for three-phase networks – ideal for power quality assessment

  • Live view of electrical parameters – immediate condition assessment

  • Measurements according to EN 61000-4-30 Class S – for maximum accuracy

  • Power calculator – supports the evaluation of energy-saving potential

  • Comprehensive protective measure testing – no additional device required

  • RCD-safe short-circuit impedance measurement – without tripping

  • Autotests – optimized, automatic test sequences

  • From test to test report – everything in one workflow


Powerful functions at a glance

Power quality analysis according to EN 61000-4-30 (Class S)

  • Voltage and current measurement (L1, L2, L3) up to 500 V / 3 kA

  • Frequency range: 40–70 Hz

  • Active, reactive and apparent power

  • Power factor (PF), cosφ, tgφ

  • Harmonic analysis up to the 40th order

  • THD evaluation (voltage/current)

  • Event recording for voltage and current

  • Energy flow measurement in four quadrants

Installation testing according to applicable regulations

  • Short-circuit impedance (also in RCD-protected circuits)

  • RCD tests (e.g. trip time, trip current)

  • Insulation measurements

  • Earth measurement including 4-wire method and specific earth resistance

  • Continuity of protective conductors / equipotential bonding

  • Illuminance (lux)

  • Phase sequence and motor rotation direction testing


Safety testing made easy

  • RCD tests in auto mode – fast, automated results

  • Individually customizable autotests – for tailored measurement routines

  • Adapter support (AutoISO-1000C) – for fully automatic insulation measurements


Power quality always in view

The integrated 3-phase power analyzer offers:

  • Live display of waveforms

  • Real-time graphics and table view

  • Phasor graph view for visualizing phase position

  • Harmonic spectrum analysis (current and voltage)

  • Simultaneous recording and display on SD card

Properties
Humidity max.: 90%
electromagnetic compatibility (EMV): EN 61326-2-2, IEC/EN 61326-1
interface: Bluetooth, USB 2.0, WiFi
measurement category: CAT III 500 V, CAT IV 300 V
operating temperature: 0 °C - +45 °C
protection rating: Housing IP 51
storage temperature: -20 - +60 °C
Weight: 2.5 kg
Width: 75 mm
Height: 223 mm
Length: 288 mm
Measurement functions Measuring range Display range Resolution Accuracy
Fault loop impedance
Fault loop ZL-PE, ZL-N, ZL-L 0.13 Ω…1999.9 Ω according to IEC 61557 0.00 Ω…1999 Ω from 0.001 Ω ±(5% v.Mw. + 30 Digits)
Fault loop ZL-PE in RCD mode from 0.50 Ω…1999 Ω according to IEC 61557 0.00 Ω…1999 Ω from 0.01 Ω from ±(6% v.Mw. + 5 Digits)
Measuring RCD parameters
RCD trip test and measuring trip time tA test current 0 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
RCD general and short-time delayed 0 ms…300 ms 0 ms…300 ms 1 ms from ±(2% v.Mw. + 2 Digits)
RCD selective 0 ms…500 ms 0 ms…500 ms 1 ms from ±(2% v.Mw. + 2 Digits)
Measuring RCD trip current RCD IA test current 0.2 IΔn…2.0 IΔn
with sinusoidal residual current (type AC) 3.3 mA…1000 mA 3.3 mA…1000 mA from 0.1 mA ±5% IΔn
with pulsating DC currents and with 6 mA DC bias (type A) 3.5 mA…700 mA 3.5 mA…700 mA from 0.1 mA ±10% IΔn
with residual DC current (type B) 2.0 mA…1000 mA 2.0 mA…