Measurement functions Measuring range Display range Resolution Accuracy
Fault loop impedance
Fault loop ZL-PE, ZL-N, ZL-L 0,13 Ω…1999,9 Ω gemäß IEC 61557 0,00 Ω…1999 Ω ab 0,001 Ω ab ±(5% v.Mw. + 0,03 Ω)
Fault loop ZL-PE in RCD mode ab 0,50 Ω…1999 Ω gemäß IEC 61557 0,00 Ω…1999 Ω ab 0,01 Ω ab ±(6% v.Mw. + 5 Digits)
Measuring RCD parameters
RCD trip test and measuring trip time tA test current 0,5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
RCD general and short-time delayed
• TN / TT system 0 ms…300 ms 0 ms…300 ms 1 ms ±(2% v.Mw. + 2 Digits)
RCD selective 0 ms…500 ms 0 ms…500 ms 1 ms ±(2% v.Mw. + 2 Digits)
Measuring RCD trip current RCD IA test current 0,2 IΔn…2,0 IΔn
for sinusoidal fault current (type AC) 3,3 mA…1000 mA 3,3 mA…1000 mA ab 0,1 mA ±5% IΔn
for pulsating DC currents and with 6 mA DC bias (type A) 3,5 mA…700 mA 3,5 mA…700 mA ab 0,1 mA ±10% IΔn
Product information

The Sonel MPI-530 is a highly advanced measuring instrument for comprehensive testing of electrical installations – both in the private and industrial sectors. It meets all requirements of the standard EN 61557 and is ideally suited for acceptance measurements according to HD 60364-6.

With its robust design, enormous measurement versatility and practical automation functions, the MPI-530 is the optimal choice for installers, test technicians and electrical experts.


🔧 Extensive functions for standard-compliant testing

The MPI-530 enables all measurements required for the safety testing of electrical systems – without any loss of accuracy:

Measurements according to standard

  • Loop impedance (also with RCD/FI switches)

  • Testing of RCDs (type AC, A, B)

  • Insulation resistance

  • Earth measurement using the 4-wire method

  • Determination of specific earth resistance

  • Continuity of protective and equipotential bonding conductors

  • Lux measurement (illuminance) with external probe

  • Phase sequence and motor rotation direction indication

📊 Power quality analysis (50/60 Hz)

  • Voltage measurement up to 500 V (L1)

  • Current measurement (up to 3 kA – depending on clamp)

  • Frequency range: 40–70 Hz

  • Active power (P), reactive power (Q), apparent power (S)

  • Power factor (PF), cosφ

  • Harmonic analysis up to the 40th harmonic

  • THD (Total Harmonic Distortion) of current and voltage


Safety testing made easy

The device enables quick and automatic performance of important safety measurements:

  • RCD test in auto mode

  • Measurement directly at the socket with WS adapter

  • AutoISO-1000C for automatic insulation testing on multi-core cables


💾 Intelligent memory structure

The memory architecture of the MPI-530 is based on a hierarchical tree structure (customer – object – room – measuring point). This allows thousands of results to be stored and evaluated in an organised manner.
A QWERTY Bluetooth keyboard facilitates data entry directly on the device.


🧭 Integrated help & graphical instructions

The MPI-530 features interactive help menus with measurement diagrams that assist with correct connection selection. Ideal for avoiding errors during setup and increasing efficiency on site.


🛡️ Robust & weatherproof – built for everyday use

  • IP54 housing: protection against dust and splashing water

  • Impact-resistant design with reinforced display cover

  • Safe working even under harsh conditions

  • Comfortable transport and use in any position


🔌 Interfaces & software solutions

  • Data transfer via USB or Bluetooth

  • Protocol creation with Sonel Reports PLUS

  • Data import/export & printing with free Sonel Reader software


🏁 Conclusion

The Sonel MPI-530 is a high-end multimeter

Properties
Humidity max.: 90%
electromagnetic compatibility (EMV): EN 61326-2-2, IEC/EN 61326-1
interface: Bluetooth, USB 2.0
measurement category: CAT III 600 V, CAT IV 300 V
operating temperature: 0 °C - +50 °C
protection rating: Housing IP 54
storage temperature: -20 - +70 °C
Weight: 2.5 kg
Width: 75 mm
Height: 223 mm
Length: 288 mm
Measurement functions Measuring range Display range Resolution Accuracy
Fault loop impedance
Fault loop ZL-PE, ZL-N, ZL-L 0,13 Ω…1999,9 Ω gemäß IEC 61557 0,00 Ω…1999 Ω ab 0,001 Ω ab ±(5% v.Mw. + 0,03 Ω)
Fault loop ZL-PE in RCD mode ab 0,50 Ω…1999 Ω gemäß IEC 61557 0,00 Ω…1999 Ω ab 0,01 Ω ab ±(6% v.Mw. + 5 Digits)
Measuring RCD parameters
RCD trip test and measuring trip time tA test current 0,5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
RCD general and short-time delayed
• TN / TT system 0 ms…300 ms 0 ms…300 ms 1 ms ±(2% v.Mw. + 2 Digits)
RCD selective 0 ms…500 ms 0 ms…500 ms 1 ms ±(2% v.Mw. + 2 Digits)
Measuring RCD trip current RCD IA test current 0,2 IΔn…2,0 IΔn
for sinusoidal fault current (type AC) 3,3 mA…1000 mA 3,3 mA…1000 mA ab 0,1 mA ±5% IΔn
for pulsating DC currents and with 6 mA DC bias (type A) 3,5 mA…700 mA 3,5 mA…700 mA ab 0,1 mA ±10% IΔn