Art-Nr.: WMDEMPI530
Sonel MPI-530 Multifunktions-Installationsprüfgerät
| Measurement functions | Measuring range | Display range | Resolution | Accuracy |
|---|---|---|---|---|
| Fault loop impedance | ||||
| Fault loop ZL-PE, ZL-N, ZL-L | 0,13 Ω…1999,9 Ω gemäß IEC 61557 | 0,00 Ω…1999 Ω | ab 0,001 Ω | ab ±(5% v.Mw. + 0,03 Ω) |
| Fault loop ZL-PE in RCD mode | ab 0,50 Ω…1999 Ω gemäß IEC 61557 | 0,00 Ω…1999 Ω | ab 0,01 Ω | ab ±(6% v.Mw. + 5 Digits) |
| Measuring RCD parameters | ||||
| RCD trip test and measuring trip time tA test current 0,5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn | ||||
| RCD general and short-time delayed | ||||
| • TN / TT system | 0 ms…300 ms | 0 ms…300 ms | 1 ms | ±(2% v.Mw. + 2 Digits) |
| RCD selective | 0 ms…500 ms | 0 ms…500 ms | 1 ms | ±(2% v.Mw. + 2 Digits) |
| Measuring RCD trip current RCD IA test current 0,2 IΔn…2,0 IΔn | ||||
| for sinusoidal fault current (type AC) | 3,3 mA…1000 mA | 3,3 mA…1000 mA | ab 0,1 mA | ±5% IΔn |
| for pulsating DC currents and with 6 mA DC bias (type A) | 3,5 mA…700 mA | 3,5 mA…700 mA | ab 0,1 mA | ±10% IΔn |
The Sonel MPI-530 is a highly advanced measuring instrument for comprehensive testing of electrical installations – both in the private and industrial sectors. It meets all requirements of the standard EN 61557 and is ideally suited for acceptance measurements according to HD 60364-6.
With its robust design, enormous measurement versatility and practical automation functions, the MPI-530 is the optimal choice for installers, test technicians and electrical experts.
🔧 Extensive functions for standard-compliant testing
The MPI-530 enables all measurements required for the safety testing of electrical systems – without any loss of accuracy:
⚡ Measurements according to standard
-
Loop impedance (also with RCD/FI switches)
-
Testing of RCDs (type AC, A, B)
-
Insulation resistance
-
Earth measurement using the 4-wire method
-
Determination of specific earth resistance
-
Continuity of protective and equipotential bonding conductors
-
Lux measurement (illuminance) with external probe
-
Phase sequence and motor rotation direction indication
📊 Power quality analysis (50/60 Hz)
-
Voltage measurement up to 500 V (L1)
-
Current measurement (up to 3 kA – depending on clamp)
-
Frequency range: 40–70 Hz
-
Active power (P), reactive power (Q), apparent power (S)
-
Power factor (PF), cosφ
-
Harmonic analysis up to the 40th harmonic
-
THD (Total Harmonic Distortion) of current and voltage
✅ Safety testing made easy
The device enables quick and automatic performance of important safety measurements:
-
RCD test in auto mode
-
Measurement directly at the socket with WS adapter
-
AutoISO-1000C for automatic insulation testing on multi-core cables
💾 Intelligent memory structure
The memory architecture of the MPI-530 is based on a hierarchical tree structure (customer – object – room – measuring point). This allows thousands of results to be stored and evaluated in an organised manner.
A QWERTY Bluetooth keyboard facilitates data entry directly on the device.
🧭 Integrated help & graphical instructions
The MPI-530 features interactive help menus with measurement diagrams that assist with correct connection selection. Ideal for avoiding errors during setup and increasing efficiency on site.
🛡️ Robust & weatherproof – built for everyday use
-
IP54 housing: protection against dust and splashing water
-
Impact-resistant design with reinforced display cover
-
Safe working even under harsh conditions
-
Comfortable transport and use in any position
🔌 Interfaces & software solutions
-
Data transfer via USB or Bluetooth
-
Protocol creation with Sonel Reports PLUS
-
Data import/export & printing with free Sonel Reader software
🏁 Conclusion
The Sonel MPI-530 is a high-end multimeter
| Properties |
|---|
| Humidity max.: | 90% |
|---|---|
| electromagnetic compatibility (EMV): | EN 61326-2-2, IEC/EN 61326-1 |
| interface: | Bluetooth, USB 2.0 |
| measurement category: | CAT III 600 V, CAT IV 300 V |
| operating temperature: | 0 °C - +50 °C |
| protection rating: | Housing IP 54 |
| storage temperature: | -20 - +70 °C |
| Weight: | 2.5 kg |
| Width: | 75 mm |
| Height: | 223 mm |
| Length: | 288 mm |
| Measurement functions | Measuring range | Display range | Resolution | Accuracy |
|---|---|---|---|---|
| Fault loop impedance | ||||
| Fault loop ZL-PE, ZL-N, ZL-L | 0,13 Ω…1999,9 Ω gemäß IEC 61557 | 0,00 Ω…1999 Ω | ab 0,001 Ω | ab ±(5% v.Mw. + 0,03 Ω) |
| Fault loop ZL-PE in RCD mode | ab 0,50 Ω…1999 Ω gemäß IEC 61557 | 0,00 Ω…1999 Ω | ab 0,01 Ω | ab ±(6% v.Mw. + 5 Digits) |
| Measuring RCD parameters | ||||
| RCD trip test and measuring trip time tA test current 0,5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn | ||||
| RCD general and short-time delayed | ||||
| • TN / TT system | 0 ms…300 ms | 0 ms…300 ms | 1 ms | ±(2% v.Mw. + 2 Digits) |
| RCD selective | 0 ms…500 ms | 0 ms…500 ms | 1 ms | ±(2% v.Mw. + 2 Digits) |
| Measuring RCD trip current RCD IA test current 0,2 IΔn…2,0 IΔn | ||||
| for sinusoidal fault current (type AC) | 3,3 mA…1000 mA | 3,3 mA…1000 mA | ab 0,1 mA | ±5% IΔn |
| for pulsating DC currents and with 6 mA DC bias (type A) | 3,5 mA…700 mA | 3,5 mA…700 mA | ab 0,1 mA | ±10% IΔn |