Product information
Testing of the differential/PE residual current measurement by qualified specialist personnel. This must be carried out in a live simulation (e.g. test transformer) to verify compliance with the set limit value as well as, in the event of this value being exceeded, the entire alarm/reporting loop of the Janitza system. This must be performed for each individual monitored incoming/outgoing circuit. The results must be documented and handed over to the specialist engineer in hardware and software form (Excel). Minimum requirements for the protocol: project name, distribution board name, outgoing circuit designation, measuring device designation, contractor name, tester name, measured value, message chain function, impressed current magnitude, type