Skip image gallery
Image similar
CCT 31.3 U - Allstromwandler AC/DC
| measuring range | 0…300 A DC / AC Ieff, variant-dependent! (rated current ranges set to standard values acc. to IEC) |
| frequency range | 0…100 kHz, any signal waveforms |
| Voltage output with AC input signal: | 2,5 ± 1 V, Ueff, AC; 2,5 ± 1,414 V (peak-to-peak) |
| Voltage output with DC input signal | 2,5 ± 1 V, DC |
| Min. burden resistance at voltage output | RB ≥ 100 kΩ |
| Output signal limitation in case of overload | < 5 V |
| Accuracy | ± 0,5 % |
| Max. operating voltage Um | 0,72 kV, Ueff |
| Insulation test voltage | 6,4 kV, Ueff, 50 Hz, 5 sec., primary conductor against measuring output/housing |
| auxiliary voltage | ± 12 V DC, ± 15%, < 70 mA, external protection via fine fuse 100 mA / 250 V, fast! |
| Step response time (90 % IPN, di/dt = 100 A / μs) | ≤ 1 μs (typ. 150 ns) |
| Signal rise rate di/dt | < 100 A / μs |
| Insulating material class | E |
| Operating altitude | ≤ 2000 m (DIN EN 61010-1) |
| Max. temperature of primary conductor | 100° C |
| Humidity | 0…95% rel. humidity, no condensation! |
Product information
Current transformer for measuring both DC and AC currents
- For use in network analysis
- and for current measurement of non-sinusoidal and distorted networks
Applied technical standards:
DIN EN 50178, 1997
DIN EN 61010-1, 2002
VDE 0160
Electrical connections:
UH + UH - 0 (Ground) IA
Spring-loaded terminal
Connection cross-sections: 0,08…2,5 mm²
Functions of the CCT 31.3 U:
- The magnetic field surrounding a current-carrying conductor is detected by a measuring core enclosing the conductor. The magnetic flux induced in the measuring core, which is directly proportional to the current in the primary conductor, is detected by means of a semiconductor component. Control electronics integrated in the device convert the signal supplied by the semiconductor into an output voltage signal directly proportional to the time profile of the measured variable.
- Due to the inductive, contactless detection of the measured variable, a galvanically isolated output signal is provided.
- The electrical contacting of the secondary circuit of the current transformer is carried out via a 4-pole spring-loaded terminal. This terminal is suitable for connecting flexible stranded wires up to 2,5 mm².
- A DC auxiliary power supply of ± 12 V is required to supply the control electronics. The auxiliary voltage inputs must be protected by a fine fuse 100 mA / 250 V / F.
Advantages and benefits of the CCT 31.3 U:
- Measurement of both DC and AC currents possible with only one current transformer.
- Wide operating frequency range from 0 Hz (DC)…100 kHz (AC).
- High electrical safety due to galvanically isolated detection of the measured variable.
- Low power requirement (≤ 2,5 VA)
- Simple and safe electrical wiring using spring-loaded terminal technology.
- Direct mounting on busbars via fastening screws integrated in the device.
- Mounting on 35mm DIN rails possible using optional snap-on mounting.
- High climatic and mechanical resistance due to PU encapsulation of all electrical components.
3D models and more files to each product can be found in our download area downloadarea
| Properties |
|---|
| Type-Name: | CCT |
|---|---|
| Type number: | 31.3 U |
| accuracy class: | 0,5% |
| ambient temperature: | -25 - +60 °C |
| bore: | Ø 28 mm |
| protection rating: | Housing IP 20 |
| storage temperature: | -40 - +90 °C |
| Width: | 70 mm |
| Height: | 92 mm |
| Length: | 48 mm |
| measuring range | 0…300 A DC / AC Ieff, variant-dependent! (rated current ranges set to standard values acc. to IEC) |
| frequency range | 0…100 kHz, any signal waveforms |
| Voltage output with AC input signal: | 2,5 ± 1 V, Ueff, AC; 2,5 ± 1,414 V (peak-to-peak) |
| Voltage output with DC input signal | 2,5 ± 1 V, DC |
| Min. burden resistance at voltage output | RB ≥ 100 kΩ |
| Output signal limitation in case of overload | < 5 V |
| Accuracy | ± 0,5 % |
| Max. operating voltage Um | 0,72 kV, Ueff |
| Insulation test voltage | 6,4 kV, Ueff, 50 Hz, 5 sec., primary conductor against measuring output/housing |
| auxiliary voltage | ± 12 V DC, ± 15%, < 70 mA, external protection via fine fuse 100 mA / 250 V, fast! |
| Step response time (90 % IPN, di/dt = 100 A / μs) | ≤ 1 μs (typ. 150 ns) |
| Signal rise rate di/dt | < 100 A / μs |
| Insulating material class | E |
| Operating altitude | ≤ 2000 m (DIN EN 61010-1) |
| Max. temperature of primary conductor | 100° C |
| Humidity | 0…95% rel. humidity, no condensation! |