Control relay, level relay, for monitoring and controlling conductive liquids. 2 output relays each with a changeover contact, LEDs for operational readiness and contact position.


  • according to IEC/EN 60 255, DIN VDE 0435-303
  • 3 electrode connections for 2-point and 1-point level control
  • high immunity to interference of the measuring circuit galvanically isolated from the mains
  • max. cable length to the electrodes: 3 000 m
  • wide setting range: 2 ... 450 k, allowing distinction between liquid and foam
  • adjustable pickup delay and release delay: 0,2 ... 20 s, separately adjustable for MIN and MAX level
  • programmable for:
    - 2 separately controlled output relays for MIN and MAX level
    - jointly controlled output relays in 2-point hysteresis level control
    - operating current principle (output relay activated in case of fault)
    - closed-circuit current principle (output relay not activated in case of fault)
  • for auxiliary voltages from 24...230 VAC or 24 VDC
  • LEDs for operational readiness and contact position
  • 2 output relays each with 1 changeover contact
  • IL 9151 and SL 9151 with safe isolation according to IEC/EN 61 140, IEC/EN 60 947-1
  • 22,5 mm width

Application
  • Level monitoring and control of conductive liquids and powders, e.g. maximum and minimum level, overfill and dry-run protection
  • Monitoring and control of the mixing ratio of conductive liquids
  • General resistance monitoring tasks, e.g. limit temperature detection with PTC
    Contact protection relay with delay


Properties
Cable lengths (max.): 5 kΩ - 3000 m, 10 kΩ - 1500 m, 35 kΩ - 500 m, 100 kΩ - 200 m, 450 kΩ - 50 m
Dimension (BxHxT mm): 22,5 x 82 x 99
Number of changeover contacts: 2
Temperature Influence: < 2 % of the set value
Type-Name: MK
Type number: 9151N.12
ambient temperature: -20 - +60 °C
auxiliary voltage: 24V AC, 42 - 48V AC, 110 - 127V AC, 220 - 240V AC, 380 - 415V AC
pickup/release delay: 0,2 - 30 s (adjustable)
protection rating: Enclosure IP 40, Terminals IP 20
setting range: 2 - 450 kΩ
switching hysteresis: approx. 3 % at 450 kΩ - 6 % at 2 kΩ