Parameter Measuring range Display range Resolution Accuracy
Measurement of mains parameters
Voltage 0 V…500 V 0 V…500 V from 0.1 V from ±(2% of rdg. + 2 digits)
Frequency 45.0…65.0 Hz 45.0…65.0 Hz 0.1 Hz ±(0.1% of rdg. + 1 digit)
Fault loop impedance
Fault loop ZL-N, ZL-L, ZL-PE from 0.13 Ω…1999 Ω
according to EN IEC 61557
0.00 Ω…1999 Ω from 0.01 Ω ±(5% of rdg. + 3 digits)
Fault loop ZL-PE in RCD mode from 0.5 Ω…1999 Ω
according to EN IEC 61557
0.00 Ω…1999 Ω from 0.01 Ω ±(6% of rdg. + 5 digits)
Measurement of RCD parameters
RCD trip test and measurement of trip time tA
Test current 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
None None None None
• RCD general and short-time delayed 0 ms…300 ms 0 ms…300 ms 1 ms from ±(2% of rdg. + 2 digits)
• RCD selective 0 ms…500 ms 0 ms…500 ms 1 ms from ±(2% of rdg. + 2 digits)
• RCD EV 6 mA DC and RCM 0 ms…10.0 s 0 ms…10.0 s from 1 ms ±(2% of rdg. + 3 digits)
Product information

Comprehensive diagnosis of the charging station with a single device

The multifunction tester EVSE-100 is a device for testing vehicle charging stations and cables for electric vehicles. With a single device, you can perform a series of tests on these objects and then create a professional test report. By appropriately simulating CP and PP circuits, the measuring device can put the charging station into various operating states. In this way, we can check the correctness of the control and perform measurements for protection against electric shock. Functional and safety tests can be carried out by simulating faults on the power supply side, i.e. the charging station (ICCB), and on the vehicle charging side (CP circuit).

Sonel MeasureEffect™

The measuring device is part of the Sonel MeasureEffect™ platform. This is a comprehensive system that allows you to perform measurements, store and manage data, and control devices on multiple levels.

Additional information

The measuring device enables the diagnosis of:

  • AC charging stations for electric vehicles with Type 2 plug with permanently connected socket or charging cable (1- and 3-phase),
  • portable charging stations for electric vehicles with Type 2 plug (1-phase and 3-phase),
  • charging cables.

Basic functions of the device

  • Simulation of PP conductor parameters:
    • open-circuit voltage,
    • 13 A, 20 A, 32 A, 63 A, 80 A.
  • Simulation of CP connection options:
    • State A – vehicle not connected,
    • State B – vehicle connected, no charging process,
    • State C – vehicle connected, charging process without ventilation.
    • State D – vehicle connected, charging process with ventilation.
  • Measurements:
    • short-circuit loop Z,
    • RCD switch parameters (AC, A, B, 6 mA DC),
    • insulation resistance RISO,
    • continuity measurement RCONT,
    • phase sequence indication,
    • coding resistance RC,
    • earth measurement RE.
  • EVSE analysis – diagnosis:
    • voltage CP+, CP-,
    • frequency f (PWM),
    • signal duty cycle D (PWM),
    • maximum charging current IMAX,
    • diagrams: CP+, CP-, f, D, IMAX,
    • switch-off time toff,
    • switch-on time ton.
  • EVSE analysis – fault simulation (ICCB, EVCS):
    • CPsh – short circuit CP to PE,
    • Dsh – diode short circuit,
    • PEop – break in PE conductor.
  • Simulation of supply circuit faults (ICCB):
    • L1op – break in phase conductor L1,
    • L2op – break in phase conductor L2,
    • L3op – break in phase conductor L3,
    • Nop – break in N conductor,
    • PEop – break in PE conductor,
    • L↔PE – L and PE cables are swapped,
    • UEXT(PE) – voltage on the PE conductor.
  • EV
Properties
Display: LCD (backlit)
Operation: Touch display
interface: Bluetooth, USB 2.0, WiFi
power supply: 230 VAC, Battery
protection rating: Housing IP 65
Parameter Measuring range Display range Resolution Accuracy
Measurement of mains parameters
Voltage 0 V…500 V 0 V…500 V from 0.1 V from ±(2% of rdg. + 2 digits)
Frequency 45.0…65.0 Hz 45.0…65.0 Hz 0.1 Hz ±(0.1% of rdg. + 1 digit)
Fault loop impedance
Fault loop ZL-N, ZL-L, ZL-PE from 0.13 Ω…1999 Ω
according to EN IEC 61557
0.00 Ω…1999 Ω from 0.01 Ω ±(5% of rdg. + 3 digits)
Fault loop ZL-PE in RCD mode from 0.5 Ω…1999 Ω
according to EN IEC 61557
0.00 Ω…1999 Ω from 0.01 Ω ±(6% of rdg. + 5 digits)
Measurement of RCD parameters
RCD trip test and measurement of trip time tA
Test current 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
None None None None
• RCD general and short-time delayed 0 ms…300 ms 0 ms…300 ms 1 ms from ±(2% of rdg. + 2 digits)
• RCD selective 0 ms…500 ms 0 ms…500 ms 1 ms from ±(2% of rdg. + 2 digits)
• RCD EV 6 mA DC and RCM 0 ms…10.0 s 0 ms…10.0 s from 1 ms ±(2% of rdg. + 3 digits)