Product information

The 3-phase energy meter EMU Professional II 3/100 TCP/IP for DIN rail mounting features an integrated TCP/IP interface with meter reading memory. The DIN rail meter has a MID B+D certification and is suitable for energy management according to ISO 50001 as well as energy cost billing.

The 3-phase three-phase meter EMU Professional II 3/100 TCP IP is suitable thanks to the Ethernet interface with Modbus TCP for integration into building control systems and smart home systems such as Loxone.
For integration into Loxone, a driver is available in the Loxone Library.

TCP/IP interface | Modbus TCP

The TCP/IP interface is integrated in the EMU Professional II 3/100 TCP/IP. The network parameters can be configured and the instantaneous measured values can be analysed on the web server. The web interface is password-protected. Connection to the LAN is via an RJ45 connector.
The EMU Professional II energy meter supports Modbus TCP communication.

  • Web page with current measured values
  • Modbus TCP
  • HTTP-Get API
  • DHCP or fixed IP
  • Buffered clock (RTC)
  • Firmware update

Functions at a glance

  • Two-way three-phase meter with TCP/IP interface
  • 3x230/400V
  • Direct connection up to 100 A
  • Accuracy class B (1%)
  • MID B+D, ex works for billing purposes
  • Access protection via password
  • Remote reading via Modbus TCP
  • HTTP-GET API

Retrieievable measured values

  • Active energy import (kWh) and export (kWh)
  • Reactive energy import (kvarh) and export (kvarh)
  • Current (A)
  • Active power (kW)
  • Reactive power (kvar)
  • Apparent power (kVA)
  • Frequency (Hz)
  • Number of voltage failures

LCD display

The LCD graphic display with a size of 38x28 mm and an LED backlighting simplifies the reading of parameters and settings while providing excellent visibility of the digits.

Configuration

Configuration is carried out on the EMU Professional II via touch-sensitive buttons.

  • Network configuration (IP address, subnet, gateway)
  • Pulse rate and time

S0 pulse output

The EMU Professional II features a configurable S0 pulse output

  • Active energy import or active energy export
  • Reactive energy import or reactive energy export

Factory configuration

  • Retrieval of network configuration via DHCP
  • Direct connection: 1'000 pulses/ 40 ms