Product information

Load monitor for monitoring electrical industrial drives for symmetrical loading of all three phases. It monitors the active power consumption of motor loads.

Features

  • according to IEC/EN 60 255, DIN VDE 0435-303
  • Detection of underload P1, overload P2, overload P1 (pre-warning stage) and overload P2 (switchable)
  • Setting of P1 and P2 via absolute scale
  • for motors up to 22 kW / 400 V or 37 kW / 690 V
  • Measuring method: active power measurement
  • large current measuring range through automatic range switching
  • 1 changeover contact each for signalling P1 and P2
  • adjustable startup override ta
  • adjustable pickup delay tv
  • with or without latching, switchable
  • Test / reset button for easy commissioning and as setting aid
  • up to 40 A without external current transformer
  • Working current principle (output relay activated in case of fault) or resting current principle (output relay not activated in case of fault)
  • Switchable optionally for single-phase loads LED indicators
  • 45 mm width


Application

The load monitor is suitable for monitoring electrical industrial drives with variable motor load. Design and function: The load monitor BH 9097 monitors the active power consumption of electrical loads. Due to the single-phase measuring principle, symmetrical loading of all 3 phases is assumed, as is usual with motor loads. Using DIP switches, the device can be configured as underload and overload monitor P1 min / P2 max. or as overload monitor with pre-warning stage P1 max. / P2 max. The settings for P1 and P2 are calibrated as absolute values in watts and are made via two rotary switches. 2 LEDs indicate the switching state of the associated output relays. The relays can be configured for working current or resting current principle. Each relay is affected by a separately adjustable pickup delay tv and a jointly adjustable startup override ta.


Measuring current (see table): A, C, E


Measuring range A B C D E F
Rated current A 40 24 8 2,4 0,8 0,24
Continuous overload 0...40 0...40 0...16 0...8 0...4 0...1
Overload 1 min. (10 min. pause) 150 150 20 16 3
Properties
Dimension (BxHxT mm): 45 x 84 x 121
Phases: 3-phase with supply voltage
Type-Name: BH
Type number: 9097.38/011
ambient temperature: -20 - +55 °C
measuring voltage: 100 - 760 VAC
protection rating: Enclosure IP 40, Terminals IP 20