Skip to main content Skip to search Skip to main navigation
0
My collective-request products

No products added yet

Go to collective request


Product information

Load monitor for monitoring electrical industrial drives for symmetrical loading of all three phases. It monitors the active power consumption of motor loads.

Features

  •  according to IEC/EN 60 255, DIN VDE 0435-303 
  •  Detection of underload P1, overload P2, overload P1 (pre-warning stage) and overload P2 (switchable) 
  •  Setting of P1 and P2 via absolute scale 
  •  for motors up to 22 kW / 400 V or 37 kW / 690 V 
  •  Measuring method: active power measurement 
  •  wide current measuring range thanks to automatic range switching 
  •  1 changeover contact each for signalling P1 and P2 
  •  adjustable start-up override ta 
  •  adjustable pickup delay tv 
  •  with or without latching, switchable 
  •  Test / reset button for easy commissioning and as setting aid 
  •  up to 40 A without external current transformer 
  •  Energized on trip principle (output relay activated in case of fault) or de-energized on trip principle (output relay not activated in case of fault) 
  •  Switchable optionally for 1-phase loads LED indicators 
  •  45 mm overall width


Application

The load monitor is suitable for monitoring electrical industrial drives with variable motor load. Design and function: The load monitor BH 9097 monitors the active power consumption of electrical loads. Due to the 1-phase measuring principle, symmetrical loading of all 3 phases is assumed, as is usual with motor loads. Using DIP switches, the device can be configured as an underload and overload monitor P1 min / P2 max. or as an overload monitor with pre-warning stage P1 max. / P2 max. The settings for P1 and P2 are calibrated as absolute values in watts and are made via two rotary switches. 2 LEDs indicate the switching state of the associated output relays. The relays can be configured for energized on trip or de-energized on trip principle. Each relay is subject to a separately adjustable pickup delay tv and a jointly adjustable start-up override ta.


Measuring current (see table): A, C, E


Measuring range A B C D E F
Rated current A 40 24 8 2,4 0,8 0,24
Continuous overload 0...40 0...40 0...16 0...8 0...4 0...1
Overload 1 min. (10 min. pause) 150
Properties
Dimension (BxHxT mm): 45 x 84 x 121
Phases: 3-phase without supply voltage
Type-Name: BH
Type number: 9097.38/001
ambient temperature: -20 - +55 °C
measuring voltage: 400 VAC
protection rating: Enclosure IP 40, Terminals IP 20